Pallet elevator operating procedures and fault analysis and processing

First, automatic

1, the inner cabinet switch on, the power indicator lights, power hoist;

2, automatic selection (the first floor to the second floor console automatic / manual self-locking knob for the manual priority), and select the desired mode of operation of the floor;

3, the goods on the roller export line, and determining the detectable photoelectric switch;

4, the photodetector 10 seconds after the commencement of the automatic transport of goods;

5, after the goods sent to the designated floor start time, when the photodetector is less than 10 seconds goods starts sending the next cargo;

6, when the vertical lifting machine should be finished as long without the switch is turned off, so as not to affect the electrical life.

Second, manual:

1. Turn on the switch inside the electric control cabinet, the power indicator light is on, and the hoist is powered;

2. Select manual gear (the automatic / manual self-locking knob of the first floor to second floor console is manual priority) and select the floor mode to be operated;

3. The desired operation is achieved by pressing the up, down, feed, and send buttons.

Third, emergency stop:

1. When an emergency situation is encountered, the emergency stop button is taken, and the hoist sound and light alarm is activated;

2. After the sound and light alarm is activated, the fault should be eliminated in time. If the time is long, the unit switch should be turned OFF ;

3. After the file is determined to be faulty, the emergency stop button is rotated and reset, and the emergency stop reset button is pressed and the mode is reselected.

Fourth, the operation notes:

1. When the vertical hoist is running, it should be determined that there is no cargo or foreign matter in the hoist elevator;

2. When the vertical hoist has an emergency problem, stop the emergency stop and record the pre-existing process;

3. When switching to manual automatically, it will work manually after the automatic program runs back to the origin;

4. When transporting the goods, the cargo should be ensured to be reliable. When the goods are inserted, it is necessary to ensure that no goods are dropped out of the pallet, and it is strictly forbidden to carry people.

V. Easily occurring faults and troubleshooting methods:

Fault phenomenon

cause of issue

Method of exclusion

The emergency stop button does not press the alarm when it is running.

1. Emergency stop button signal line is broken
2. When lifting, the entrance and exit raceway line has foreign objects or goods inclined
3. Inverter or protection failure

1. Check the emergency stop button signal line break and connect
2. Remove the foreign object or put the goods in order

3. Check the lifting motor and the inlet and outlet roller line motor or inverter to protect and contact the manufacturer in time.

Automatic or manual program confusion

1. PLC burned out
2 signal line connection error, short circuit, signal detection component damage
3. Damage to low-voltage electrical components in the cabinet

1. Contact the manufacturer in time to replace the PLC2. Incorrect connection: check the signal line node and correct it.
Short circuit: Whether the signal line and its contact are well insulated. Signal detection component is damaged: contact the manufacturer for replacement.

There is abnormal noise during operation

After long-term use of the machine, mechanical parts wear out for a long time, causing mechanical deformation.

Contact the manufacturer and coordinate the solution

 